How Do Harmonics Affect Power Factor Correction?

Posted by James Keys on Mar 18, 2020 8:55:00 AM

total-harmonic-distortion-voltage

In recent years the way electricity is used has changed significantly. Developments in semi-conductor technology have created a major increase in thyristor and converter-fed loads. Electronic equipment, particularly that using solid state devices, can have a detrimental effect on the electrical power system in a facility to the point where operation of electrical and electronic equipment is disrupted. Solid state devices generate Harmonics into the electrical system, i.e. they generate frequencies that are integer multiples of the fundamental line frequency of 60 Hz. The harmonics lead to a higher capacitor current, because of the higher frequencies that are attracted to the capacitor. The impedance of the capacitor decreases as the frequency increases.

Harmonic distortion can result in any or all of the following:

  • Premature failure of capacitors
  • Nuisance tripping of circuit breakers and other protective devices
  • Failure or malfunctioning of computers, motor drives, lighting circuits and other sensitive loads

The rising capacitor current can be accommodated by design improvements of the capacitor. However, resonating circuits may occur between the power factor correction capacitors and the inductance of the feeding transformer as well as the main feeders. If the frequency of such a resonating circuit is close enough to a harmonic frequency, the resulting circuit amplifies the oscillation and leads to immense over-currents and over-voltages.

De-tuned Capacitor Banks

The installation of de-tuned (reactor-connected) capacitors is designed to force the resonant frequency of the network below the frequency of the lowest harmonic pre-sent. This ensures that no resonant circuit and no amplification of harmonic currents exist. Such an installation also has a partial filtering effect, reducing the level of voltage distortion on the supply, and is recommended for all cases where the share of harmonic-generating loads is more than 20% of overall load to be compensated.

Tuned Filtered Capacitor Banks or Harmonic Filter

A filter circuit presents a very low impedance to the individual harmonic current diverting the majority of the current into the filter bank rather than the supply. The resonance frequency of a de-tuned capacitor is always below the frequency of the fifth harmonic.

Reactive Power Compensation can be properly planned with the aid of the diagram shown below.

planning reactive power compensation

 


 

 

Topics: power factor correction, harmonic distortion

Drive Your Operation Forward

IDS is dedicated to solving your automation and motor control needs. Since 1988, we have been building solutions that have helped our clients transition established equipment to something that is compatible with the demands of today. We want to share our knowledge with you!

Our knowledge base contains:

  • Tips for designing and servicing your motor control system
  • Information about the machines and processes we provide services for
  • How to improve your operating costs
  • Where you can find assistance to finance your improvements

Subscribe Here!

Recent Posts